IN Brief:
- The InterLink Converter provides an interface between AC and DC electrical architectures.
- Solid-state circuit breakers use semiconductor switching to interrupt DC current rapidly.
- Schneider Electric is also introducing software-defined distribution and TeSys iMCC motor control technologies.
Schneider Electric has unveiled a portfolio of power electronics technologies for electrical distribution, combining semiconductor switching, sensing, digital controls, and communications across protection equipment, power converters, and industrial motor control systems.
Presented on 24 November at the McLaren Technology Centre in Woking, the portfolio comprises solid-state circuit breakers for DC protection, an InterLink Converter for AC/DC interfaces, software-defined low-voltage distribution, and TeSys iMCC motor control. The equipment was showcased at the launch of Schneider Electric’s Partnerships for Innovation initiative, which brings together industry partners to develop electrical distribution technologies.
The company is targeting installations where conventional alternating current distribution must accommodate increasingly extensive use of direct current equipment, including photovoltaic generation, batteries, vehicle charging, and high-density computing. These installations contain multiple sources and loads, each with its own conversion, protection, and control requirements.
Mechanical circuit breakers interrupt current by separating conductive contacts and extinguishing the resulting arc. In an AC system, periodic current zero crossings help the interruption process. Direct current does not have that natural zero crossing, requiring the protection device to interrupt current and manage energy stored in the circuit by other means.
A solid-state circuit breaker uses semiconductor devices that can be switched into a non-conducting state electronically. Power electronic components can switch in microseconds, reducing the time during which a fault may affect other connected equipment. The overall clearing time depends on how quickly the system detects a fault and how the breaker manages the stored energy during interruption. Schneider Electric has not supplied individual device ratings or fault clearing times in its November material.
Limiting fault duration can help protect converters connected to a common DC bus, where several power sources may contribute to a fault. Capacitors within converters can discharge rapidly into a short circuit, while battery systems may continue supplying current unless the relevant electrical path is interrupted. Protection engineers must establish the possible contributions from each source and coordinate branch protection so that unaffected equipment can continue operating where the design permits.
Solid-state switching also changes the thermal characteristics of protection equipment. Semiconductor devices dissipate energy while conducting current, creating cooling requirements that differ from those of mechanical contacts. Hybrid designs can combine electronic interruption with mechanical isolation, but the architecture must be selected against requirements for electrical losses, isolation, fault current capability, and maintenance.
Schneider Electric’s InterLink Converter addresses the interface between AC and DC distribution. Conventional installations may convert photovoltaic DC output to AC for distribution and subsequently convert it back to DC for battery charging or electronic loads. A hybrid architecture can provide an alternative route between compatible DC equipment while retaining an AC supply for other loads.
Reducing the number of conversion stages can lower electrical losses, although the outcome depends on the efficiency of the individual converters and the operating profile. An AC/DC interface must also maintain the required electrical conditions on both sides of the conversion stage as generation and consumption change. Its voltage rating, isolation arrangement, and response to abnormal conditions determine how it can be incorporated into a distribution design.
The portfolio’s software-defined distribution equipment and TeSys iMCC motor control technology extend digital configuration and monitoring into low-voltage systems. Conventional motor starters combine switching devices, overload protection, and control circuits; intelligent assemblies can make operating information available to supervisory systems and allow compatible settings to be managed electronically.
Changes to settings must remain consistent with the installation’s electrical protection study. Remote configuration can simplify commissioning and maintenance, but access controls and change management become increasingly important where incorrect settings could affect coordination between protective devices. Safety functions must also remain available when communications with a supervisory system are lost.
Schneider Electric’s wider partnerships programme will involve collaboration with organisations working on electrical infrastructure for buildings, data centres, transport, and industry. It follows a separate strategic partnership with engineering consultancy Arup disclosed earlier in November, covering the development of physical and digital energy infrastructure.
Changes in the distribution topology may also require a fresh assessment of fault levels rather than reuse of protection settings from an earlier installation. The four technologies presented in Woking cover different functions within the same electrical system. Their eventual application will depend on the detailed equipment specifications, including converter efficiency, interrupting capacity, voltage limits, and compliance with applicable installation standards. Schneider Electric has not provided a commercial availability timetable for individual portfolio elements.