Hitachi Energy wins Irish 400 kV grid projects

Hitachi Energy wins Irish 400 kV grid projects

Hitachi Energy will supply compensation technology for three Irish substations. ESB Networks is deploying TCSC systems on its 400 kV infrastructure to control flows and increase potential transfer capability.


IN Brief:

  • The contract covers Oldstreet, Dunstown and Knockkyle on Ireland’s 400 kV transmission system.
  • Thyristor-controlled series compensation adjusts effective line reactance to influence AC power flows.
  • Hitachi Energy says transfer capability could increase up to twofold on two lines and threefold on the Dunstown line.

Hitachi Energy has been selected by ESB Networks to supply thyristor-controlled series compensation equipment for three projects on Ireland’s 400 kV electricity transmission network. The installations are planned at Oldstreet in County Galway, Dunstown in County Kildare and Knockkyle in County Laois. They are intended to give system operators greater control over power flows and make more transfer capacity available on existing transmission corridors.

The selected systems use thyristor-controlled series compensation (TCSC), a form of flexible alternating current transmission system technology. Hitachi Energy’s contract covers design, supply, installation and commissioning, as well as long-term lifecycle support. Neither a contract value nor a commissioning timetable has been disclosed, so the projected capacity improvements remain design outcomes rather than completed grid upgrades.

On an alternating current line, inductive reactance influences the relationship between voltage angle and active power transfer. Adding a capacitor in series offsets part of that reactance; a thyristor-controlled branch allows effective compensation to be adjusted while the circuit is in operation. Changes in the compensation setting influence where power flows across connected circuits. The equipment does not create additional generation or remove the thermal and stability limits imposed elsewhere on the transmission network.

Ireland’s growing share of weather-dependent generation increases the need for adjustable power flow control. Wind output may rise at one location while demand is concentrated elsewhere, and flows between transmission substations can change as generation and consumption vary. A transmission line can reach operational constraints even when other parts of the network still have spare physical capacity. Controlling effective series reactance may improve how existing corridors share those flows, although system security and equipment ratings continue to determine the actual permissible transfer limits.

Hitachi Energy says the selected compensation levels could raise transfer capability to as much as twice the current level on the Oldstreet and Knockkyle lines, and as much as three times on the Dunstown line. These are stated potential increases for particular circuits under the proposed arrangements. They should not be interpreted as a doubling or tripling of total Irish transmission capacity, or as power already flowing at those levels.

Series compensation can also affect the dynamic response of the network. At particular operating conditions, an electrical resonance below the 50 Hz system frequency can interact with connected rotating machines, producing subsynchronous resonance. Hitachi Energy says its TCSC design helps mitigate that risk while controlling line reactance. Detailed network modelling, protection settings and commissioning tests will be needed to confirm the system response once the equipment is installed.

The work falls within Ireland’s Price Review 6 investment programme for 2026–2030. EirGrid brings forward the priority transmission project portfolio in its role as transmission system operator, while ESB Networks delivers the onshore infrastructure as transmission asset owner. The division of responsibilities means the physical equipment must be integrated with operating and protection requirements established for the wider transmission system, rather than being assessed as an isolated substation modification.

The projects form part of a broader response to changing generation and demand patterns. Figures cited by Hitachi Energy indicate that Irish grid-scale solar capacity exceeded 1 GW during the first half of 2026, while solar’s reported share of the electricity mix in June rose to 8.2%, from 5.3% a year earlier. Fluctuating wind and solar output makes the direction and magnitude of flows more variable, although the equipment must also accommodate conventional demand and network contingencies.

Increased transfer capability may help connect generation with load without relying exclusively on new overhead routes, but installing TCSC equipment still involves significant electrical and civil engineering. The systems need space and appropriate connections at the existing high-voltage substations. Their deployment also entails commissioning tests for switching behaviour, measurement systems, control response, and fault protection under representative operating conditions before their settings can be integrated with normal network dispatch.

Because Oldstreet, Dunstown and Knockkyle occupy different parts of the 400 kV system, the value of each installation depends on the behaviour of the surrounding circuits. Increased transfer on one corridor can move a constraint to another transformer, breaker or line unless network-wide limits are reflected in control settings. The project therefore requires coordination between ESB Networks as transmission asset owner and EirGrid as transmission system operator, as well as integration with the protection systems already installed.

The contract will take the three projects into detailed design and implementation under Ireland’s Price Review 6 programme for 2026–2030. Their eventual contribution to secure power transfer will depend on commissioning results and the operational limits set by EirGrid. No individual completion dates have yet been announced.